A Station in Minutes from the Library
The Device Library installs ready-made device packages from the website onto this server. A package contains all the tags of the device, its calculated tags and working screens (a 3D main screen plus settings screens). You only enter a few details such as the name and IP. Packages: Well, Tank, Pump Station, DMA and PRV stations (CP110, AquaCnt and Omron variants); as the list grows on the site it appears here too.
| Channel + device | Created with the right driver and communication settings (an existing channel with the same name is reused). |
| Tags | The register map of the device: 113–560 ready tags depending on the product (address, scaling and type filled in). |
| Calculated tags | Derived values such as efficiency, cost and fill level (Advanced Tags). |
| Screens | Main screen + settings sub-screens; water level, flow and status colors are bound live. |
| Background images | The light, dark and marine theme images of the 3D main screen. They come inside the package and are written to the server during installation. |
Installing (step by step)
- On the SCADA page press New Screen and choose the Device Library card.
- Find the device: type a brand, model or protocol in the box at the top, or narrow the list with the category buttons. Clicking a card shows what the device does, what the package contains and what will be asked during installation.
- Tick Select on the devices you want (several can be selected) and press Install selected.
- In Install details enter, for each device, the channel name, the device name and the requested details (IP address, port, unit / node number, station parameters). If you install the same package a second time, give it a different device name; screens and calculated tags are created for the new name. If a problem is shown in red (name conflict, empty IP), fix it first.
- Press Install. The window shows the progress: channel, device and tags, calculated tags, background images, screens. A device with hundreds of tags takes a few seconds.
- In the result window press Open screen: the main screen opens. If the device answers at that IP, values appear immediately.
.mhpkg.json); on this server choose it with Import from file in the Device Library window. Installation continues with the same steps; the images are inside the file.Background, Theme & Water Settings
The background of the main screen is a professional 3D drawing and follows the application theme: when switching between light, dark and marine, the background changes to its theme counterpart; the saved definition of the screen does not change.
Water level bindings: in design mode, clicking the water group shows the "Level tag / Height / Fill margin" fields in the properties panel. If the tank height is not in the PLC, a manual constant value can be entered; the animation works with the correct ratio.
The animation list (⚡) lists all the animations of the screen with a "template" badge: which tag drives which object is visible at a glance, and clicking a row highlights the object on the canvas.
Where are the images kept?
| Location | In the data folder of the server (korubin-art), not in the program folder; they are not deleted by an upgrade and are included in the automatic backup. |
| When they are written | While a package is installed, before its screens. An image that is already on the server is not written again. |
| Security | Only a user with SCADA edit permission can upload an image. Because the image is placed inside the page, its content is checked: a file carrying script or external links is rejected. |
If the background does not appear
If the screen shows the red text "Screen background not found", the screen, device and tags are intact; only the image is missing on the server. A project package carries the images (since 3.10.0); this text appears when the package was prepared with an older version that does not carry images, when it was installed by an older app that does not upload images, or when the import finished incompletely (see After the import: what is where). If the screen came with a project package, first import the package again in Merge mode; if it was installed from the device library, follow the steps below.
If the box says something else, the cause is different: if it reads "The background image could not be loaded" and mentions sign-in or permission, sign in again (viewing screens needs the SCADA permission); if it says "the image arrived but could not be drawn", refresh the page with Ctrl+F5. The small line under the box shows the address of the image and the detail.
- Open New Screen → Device Library.
- Tick Select on the device of the screen whose background is missing.
- Press Upload background images only at the top. Only the images are uploaded; no channel, device or screen is created.
- Reopen the screen.