A counter turns a tag value into period consumption: this hour, today, this week, this month, this year and the previous ones. A metric is an indicator computed from counters with a formula (m³/ton, kWh/m³, loss percentage). The water footprint, water efficiency and the flow diagram are built on these two. Page: Add-ons › Counters and Metrics in the left menu; it is shown on every installation.
Three concepts
| Concept | What it tells you |
|---|---|
| Counter | Period consumption from a tag: how many m³ today, how many kWh this month. |
| Category | What the counter measures: water production / supply, water consumption, wastewater / discharge, electricity consumption… |
| Group | Where the counter is: Plant 1 › Water supply. Metrics and the water reports select counters in bulk by category and group. |
Counter types
| Type | When |
|---|---|
| Rate | The tag gives an instantaneous flow or power; it is integrated over time (m³/h → m³, kW → kWh). |
| Device totalizer | The device gives its own index; resets and rollovers are compensated. |
| Accumulate deltas | An increasing raw counter (pulse counter); successive differences are added up. |
| On / off | A "running" signal; runtime is accumulated. |
| Sum of counters | The sum of the counters in the same series. |
| Manual | Nothing is measured; the period value is entered by hand (invoice, estimate, laboratory). |
Adding the first counter
- Click Add counter.
- Enter a name (e.g. Well 1). The code is generated from the name (Well1); the counter's output tag becomes
_Counters.Well1. - Choose the type. If you measure an instantaneous flow or power, pick the Preset that matches your input unit (e.g. m³/h → m³, L/s → m³); multiplier, divisor, time base and unit are filled in.
- Choose a category and a group (e.g. Water production / supply, Plant 1 › Water supply). A new group is created from the same list.
- Type the input tag or pick it from the tag tree (e.g. Field.Well1.Flow).
- Save. The counter appears in the list; within a few seconds the Today column starts to increase.
Series, gate tag, filters, reset and rollover settings are under Advanced settings; most counters never need them.
Manual counters
For unmetered items (a mains invoice, an estimate, a laboratory figure) add a counter of type Manual. Then click the counter, choose Enter period value, select the period and type the value. Manual counters are usually filled in monthly.
Data reliability
| Situation | What happens |
|---|---|
| Data gap | If communication is lost, the consumption in between is estimated and kept separately as the estimated share; reports mark it with a warning icon. |
| Reset / rollover | If the device index drops or wraps at its capacity, consumption is not lost; the event is logged. Optionally the counter stops and waits for an operator decision. |
| Spike | Increases that are physically impossible (maximum rate limit) are filtered out. |
| Manual correction | A period value can be corrected; the correction is stored apart from the measured value, with who made it and when. |
| Meter replacement | When the device is replaced, the old final index and the new initial index are entered; the total continues without a break. |
Categories and groups
Names are managed in one place: the Categories and groups button above the counter list.
- Built-in categories (water production / supply, water consumption, wastewater / discharge, electricity consumption…) are used by the water reports; they cannot be renamed or deleted.
- You can add your own categories (compressed air, steam, chemicals…); they can be renamed, merged and deleted.
- Groups form a tree (up to 8 levels). A metric that selects a group also counts its sub-groups.
- Rename and delete work in two steps: Continue shows what will change, Apply writes it. The window warns you if the set of counters a metric selects would change.
Metrics
A metric is an indicator computed from counter and tag values. In the formula, inputs are referenced as {Name}:
{Water} / {Production} → m³ / ton
({In} - {Out}) / {In} * 100 → loss %
| Input | What it gives |
|---|---|
| Tag | The current value of a tag. |
| Tag set | The current sum, average, minimum, maximum or count of several tags (e.g. Wells.*.Flow). |
| Counter | A single counter, or several chosen by a category / group selector. |
| Metric | The value of another metric for the same period. |
| Manual input | A value entered per period: production quantity, headcount, laboratory result, rainfall. |
| Constant | A fixed number (a limit, a conversion factor). |
An instant metric is computed from current values, a period metric from the data of the chosen period. Every result carries a quality:
| Quality | Meaning |
|---|---|
| good | All inputs were measured. |
| estimated | Contains an estimated share or a data gap. |
| partial | Some counters have no data for that period, or some tags in a tag set give no value. |
| none | Could not be computed; the reason is shown next to it. |
Formula library
On the Metrics tab, Add from formula library opens the ready formulas: pump efficiency, hydraulic power, pump head, pipe velocity, Hazen-Williams head loss, water loss ratio, specific energy (kWh/m³), per-capita consumption, capacity utilisation, change against the previous period… Pick a formula, bind only its inputs, check the result with Try, and save.
Breakdown: what is this number made of?
Click a row in a metric's period series, a number in the water footprint table or a water efficiency indicator: the formula, the values that went into it and the contribution of every counter open. Counters with no record for that period show "no data"; that is the reason for the "partial" mark next to the number.
Output tags
Every counter and metric also exposes its value as a tag, used like any other tag in alarm definitions, data logging, SCADA screens and Data Bridge agents.
| Tag | Value |
|---|---|
_Counters.<Code> | Cumulative value. |
_Counters.<Code>.Hour / .Day / .Week / .Month / .Year | Consumption of the current period. |
_Counters.<Code>.PrevHour … .PrevYear | Consumption of the previous period. |
_Metrics.<Code> | The current value of an instant metric; today's value of a period metric. |
The same outputs are published on the OPC UA server under the _Counters and _Metrics folders. For reports and external systems see Reports and export.