Protocol · BACnet/IP

BACnet/IP — building automation on one screen

Bring HVAC, lighting and energy controllers into your SCADA. MergenHub finds BACnet devices on the network, builds the tags from their object lists and serves the values over OPC UA, REST and web SCADA.

← All protocols & modules
MergenHub — BACnet/IPConnected
Project
▾Connectivity
▾BACnet
▪AHU_Floor3
AHU_Floor3 · Device 1001 · 10.20.4.31
DriverBACnet/IP (UDP 47808)
Device Instance1001
Write priority16
COVEnabled
BBMD—
TagAddressValueQuality
Supply_TempAI:118.4Good
Return_TempAI:223.1Good
Fan_CommandBO:11Good
SetpointAV:321.0Good
ModeMSV:52Good

The MergenHub interface — a BACnet/IP air handling unit: Analog Input, Binary Output and Multi-state Value objects.

What is BACnet?

BACnet (ASHRAE 135 / ISO 16484-5) is the common language of building automation devices. BACnet/IP reads and writes objects (Analog Input, Binary Output, Multi-state Value…) and their properties over UDP 47808.

Where is it used?

Air handling units, chillers, fan coils, lighting and energy meters in hospitals, malls, offices, data centres and factory buildings. At water and energy sites the building side is monitored in the same SCADA.

Driver capabilities

Feature coverage

MergenHub joins the BACnet network as a client; the protocol layer is written inside the driver, with no external library.

Discovery

Network search (Who-Is)

The device wizard lists the BACnet devices on the network; the selected device's instance, IP, network number and MAC are filled in.

Tag generation

From Object_List

Tags are built from the device's object list: tag name from Object_Name, description from Description. Large lists arrive in one request with segmented responses.

Reads

Block reads

Block reads with ReadPropertyMultiple; devices without RPM fall back to ReadProperty automatically.

Writes

Priority writes

Writes with WriteProperty; priority from the device setting (default 16) or the address (BO:2@8). Writing null to a text tag relinquishes the priority.

Events

COV subscription

Optional Change of Value subscription: the device reports when the value changes; devices without COV are polled.

Network

BBMD and MS/TP

BBMD (foreign device registration) for devices on other subnets; network number + MAC for MS/TP devices behind a router.

Object and service support
AI / AO / AVBI / BO / BVMSI / MSO / MSVDevicePresent_ValuePriority_ArrayStatus_FlagsReadPropertyMultipleWritePropertySubscribeCOVWho-Is / I-AmSegmentation
Control safety

Quality comes from the device status

GuaranteeIf the device does not answer, the tag is Bad; Fault or Out_Of_Service in Status_Flags shows as Uncertain. An object the device does not have is marked Bad and leaves the scan; forged COV notifications are ignored.